Specifications

 

 

Model No.Rated CurrentTurns RatioOutput CurrentLoadInsulation VoltagePhase ErrorAccuracy
ACDC
DCT006P6A4.3 A1:2500 2.4mA10Ω/20Ω>4kV/1min<15'0.1 Class
DCT101P60 A43 A24mA10Ω/20Ω>4kV/1min<15'0.1 Class
DCT104P100 A72A40mA12.5Ω>4kV/1min<15'0.1 Class
DCT105P120 A85 A48mA12.5Ω>4kV/1min<15'0.1 Class

 

Outline Dimensions (Unit: mm) 

Model No.ABCDEFG
DCT006P8.230.130.11519.31518.8
DCT101P8.230.130.11519.31518.8
DCT104P13393825331315
DCT105P13393825331315

 

Drawings
60A 100A/120A
Characteristics

Dielectric Strength: not less than 4kV/1mA/1min.

Insulation Resistance: >500MΩ (500VDC).

Operating Temperature : -40~ +85.

Relative Humidity: 95% ( 25) Altitude: 10000m.

 AC measurement capacity is 20% higher than rated current.

 High Precision. suitable for kWh meter Class 0.2, Class 0.5, Class 1.0.

 Typical AC current measurement error is within 0.02% at Ib test point.

 Typical phase shift is at 1-10' , additional compensation is not needed.

 Very reliable and stable performance at different temperature conditions.

 Good linearity, it support automatically software calibration.

 Different type for different fixing and assembly easily.

 Quick connection to PCB available on request.

ROHS Compliance is available on request.